Refrigerant global warming potential and the HFC phase down

Updated

Global warming potential is not an environmental footnote on a refrigeration site. It decides your gas price, your leak check interval and whether your plant has a future.

Get refrigeration quotes Two minutes of questions; refrigeration engineers covering your site quote you directly. Free, no obligation.

The phase down, in one line

Gov.uk states that the UK is phasing down HFCs by 79% by 2030, measured against average HFC use between 2009 and 2012. The phase down also applies to mixtures containing these gases (Environment Agency and Defra). Less supply of high global warming potential gas means higher prices for the gases that older plant was designed around.

Refrigerant GWP: R407C, R134a and the other gases you will meet

Global warming potential of common refrigerants, as published by gov.uk (figures rounded to the nearest whole number)
RefrigerantGlobal warming potentialCharge equal to 5 tonnes carbon dioxide equivalent
R404A3,9221.3kg
R507A3,985Calculate from the published GWP
R410A2,0882.4kg
R407C1,774Calculate from the published GWP
R134a1,4303.5kg
R448A1,386Calculate from the published GWP
R32675Calculate from the published GWP

The global warming potential column is taken directly from the gov.uk F gas tables. The kilogram column is only filled in where gov.uk publishes the worked figure itself, in its leak checking guidance.

For any other gas, ask your contractor to calculate and record the carbon dioxide equivalent of your actual charge rather than working from a figure copied off a web page.

What that means for old plant

  • High global warming potential means short leak check intervals. The same physical charge of R404A crosses a threshold at roughly a third of the weight of R134a.
  • It also means expensive top-ups. Restricted supply of the highest global warming potential gases has been pushing costs up, which turns a chronic leak into a serious operating expense.
  • Conversion is a real option, not always the right one. Retrofitting a lower global warming potential blend changes capacity, oil compatibility and sometimes component selection, so it needs designing, not just decanting.
  • Natural refrigerants change the compliance picture. Ammonia, CO2 and hydrocarbons sit outside the F gas leak check regime but bring their own safety duties, and CO2 systems run at pressures that raise pressure equipment questions.

There are also restrictions on using certain F gases to refill equipment, and bans on F gas in some new products. Both are published on gov.uk and both change over time: check the current guidance before committing to a refrigerant for new plant.

Get refrigeration service and repair quotes

Two minutes of questions; refrigeration engineers covering your site quote you directly. Free, no obligation.

Your plant

What needs attention?

  • Free, no obligation
  • Your details go to at most three engineers
  • Takes about two minutes

Questions, answered directly

What is the GWP of R407C?

1,774, as published in the gov.uk F gas tables. On that figure, 5 tonnes carbon dioxide equivalent, the threshold for annual leak checks, is a charge of about 2.8kg. Ask your contractor to calculate and record it for your actual charge.

What is the global warming potential of R134a?

1,430 in the gov.uk F gas tables. Gov.uk's own worked figure puts 5 tonnes carbon dioxide equivalent at 3.5kg of R134a, 50 tonnes at 35kg and 500 tonnes at 350kg.

Is R407C being phased out in the UK?

R407C is a mixture of HFCs, and gov.uk states the phase down covers such mixtures. That means a 79% cut in HFC supply by 2030 against average use in 2009 to 2012: a squeeze on supply, not a single phase-out date. Gov.uk publishes separate guidance on F gases banned for refilling equipment; check it before planning an R407C refill.

Is R404A banned in the UK?

No single ban date: a phase down plus restrictions, with separate gov.uk guidance on refill bans and new-product bans. Gov.uk states HFCs are phasing down 79% by 2030 against 2009 to 2012 average use. R404A has one of the highest global warming potentials in common use, so supply and price pressure fall hardest on it. Check current guidance first.

Should I convert my system to a lower GWP refrigerant?

Often yes on cost grounds, but it is an engineering decision rather than a swap. Capacity, oil compatibility, expansion device selection and sometimes seals and components all change with the refrigerant. Get the calculation and a written scope from a certified contractor, and compare it against the whole-life cost of replacement plant rather than against a single top-up.

Sources

This site's own datasets, every figure quoted from its source and dated:

  • The Fgas Duties and Thresholds carries 5 published figures read from 2 sources' own pages, from 3 to 12 month, read 7 November 2026.
  • The Refrigerant GWP and Phase Down carries 3 published figures read from 2 sources' own pages, under different breakdowns, so no one range is stated, read 7 November 2026.
  • The median published figure in the Refrigeration Service Price Index is 135 GBP across 10 figures from 6 sources' own pages (range 60 to 450 GBP), read 11 November 2026.
  1. gov.uk. Checking F gas equipment for leaks
  2. gov.uk. Record F gas in equipment you own or service
  3. gov.uk. Fluorinated gases (F gases), global warming potentials
  4. gov.uk. Certification for companies working on equipment containing F gas
  5. gov.uk. Qualifications required to work on equipment containing F gas
  6. legislation.gov.uk. Pressure Systems Safety Regulations 2000, Schedule 1